Calculation Process for Configuring AHF Modules
To accurately configure AHF modules, we need to consider the following parameters:
- Transformer Capacity: 2000 kVA
- System Voltage: 400 V
- Total Current: 75% of rated current
- Current THDi: 35%
- Target THDi: 5%
- Redundancy Factor: 30%
Step-by-Step Calculation
Determine the Rated Current of the Transformer:The rated current Irated of the transformer is calculated using the formula:
Conclusion
By following the detailed calculation process outlined above, we determined that 4pcs 200A AHF modules are needed to achieve the desired reduction in THD, considering a 30% redundancy factor. This accurate calculation ensures the optimal configuration of AHF modules, enhancing power quality and system reliability.